SPS 318.1803Inclined platform lifts.
(1)Runways. Substitute the following wording for the requirements in ASME A18.1 section 3.1.1: Inclined platform lifts shall be installed so that the necessary means of egress is maintained as required in the building code. For new installations, the egress width shall be measured with the inclined platform lift in the unfolded, usable position. For replacement of a previously approved inclined platform lift, the egress width may remain as it has been with the original lift in place, but may not be reduced by the replacement.
(2)Lower level access ramps and pits.
(a) Substitute the following wording for the requirements in ASME A18.1 section 3.1.4.1: Ramping inclinations for floor-mounted ramps shall be in accordance with the building code.
Note: Under the building code, a floor surface steeper than 1:48 within the required wheelchair-maneuvering clearances at a lift entrance is a ramp, and a lift entrance at a ramp must have a power-opening device. Clearances to the lift call and door-opener button must also meet the building code.
(b) Substitute the following wording for the requirements in the last sentence and pars. (a) to (e) of ASME A18.1 section 3.1.4.2: When in use, the inclination of retractable ramps shall be in accordance with the building code.
(3)Operating devices. Substitute the following wording for the requirements in A18.1 section 3.10.1: Operation of the lift from the landings and platform shall be controlled by continuous-pressure-type switches. The operating devices shall be designed so that both the up and down circuits cannot be operated at the same time.
Note: See the building code for requirements relating to accessible controls, operation, and signage.
History: CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14.
SPS 318.1804Inclined stairway chair lifts. Substitute the following wording for the requirements in ASME A18.1 section 4.1.1: Stairway chairlifts shall be installed so that the required means of egress is maintained as required in the building code. For new installations, the egress width shall be measured with the stairway chair lift in the unfolded, usable position. For replacement of a previously approved stairway chair lift, the egress width may remain as it has been with the original lift in place, but may not be reduced by the replacement.
Note: Stairway chairlifts complying with this section may be installed as a convenience for individuals but are not recognized by the building code as providing accessibility due to the inability of a wheelchair user to use them without assistance.
History: CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14.
SPS 318.1808Hydraulic driving means. These are department rules in addition to the requirements in ASME A18.1 section 8.1:
(1)Shutoff valve.
(a) A manually operated shutoff valve shall be provided between the hydraulic pump unit and the hydraulic cylinder.
(b) For a lift with a machine room, the shutoff valve under par. (a) shall be located inside the machine room and adjacent to the hydraulic pump unit.
(2)Pump relief valve.
(a) General. Each pump or group of pumps shall be equipped with one or more relief valves conforming to all of the following, except as specified in par. (b):
1. Be located between the pump and the check valve.
2. Be of such a type and so installed in the bypass connection, that the valve cannot be shut off from the hydraulic system.
3. Be of sufficient size, individually or accumulatively, to pass the maximum rated capacity of the pump without raising the pressure more than 50% above the working pressure. Two or more relief valves may be used to obtain the required capacity.
4. Be sealed after being set to the correct pressure.
(b) No relief valve. A relief valve is not required for centrifugal pumps driven by induction motors, provided the shut-off, or maximum pressure that the pump can develop, is not greater than 135% of the working pressure at the pump.
(3)Check valve. A check valve shall be provided that will hold the platform lift with the rated load at any point if either of the following occurs:
(a) The pump stops and the down valves are closed.
(b) The maintained pressure drops below the minimum operating pressure.
(4)Pressure-gauge fittings. A pressure-gauge fitting with a shutoff valve shall be provided at either of the following locations:
(a) On the cylinder side of the check valve.
(b) Immediately adjacent to the hydraulic control valve.
(5)Type tests, certification, and marking plates for control valves.
(a) Engineering tests and certification process. Each type or model and make of a hydraulic control valve shall be subjected to the engineering tests and to the certification process specified in ASME A17.1 section 8.3.5, except ASME A17.1 section 8.3.5.3.1 does not apply.
(b) Hydraulic controls. Hydraulic control valves shall be plainly marked in a permanent manner with all of the following information:
1. The certifying organization’s name or identifying symbol.
2. The name, trademark, or file number by which the organization that manufactured the product can be identified.
3. Type designation.
4. Component-rated pressure.
5. Electrical coil data.
History: CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14.
SPS 318.1809Rope sockets. This is a department rule in addition to the requirements in ASME A18.1 section 9.8: Where wedge rope sockets are provided, they shall conform to the requirements in ASME A17.1 section 2.20.9.5.
History: CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14.
SPS 318.1810Routine, periodic, and acceptance inspections and tests.
(1)Inspectors. The requirements in ASME A18.1 sections 10.1.1 to 10.1.4 are not included as part of this chapter.
Note: See s. SPS 318.1011 for additional requirements relating to inspections
(2)Applicability of inspection and test requirements. Substitute the following wording for the requirements in ASME A18.1 section 10.1.5: Inspections and tests required by subs. (4) to (8) are to determine whether the equipment conforms to whichever of the following are applicable:
(a) The standard in effect on the contract date for the original installation.
(b) For altered components, the standard in effect on the contract date for the alteration.
(3)Installation placed out of service. Substitute the following wording for the requirements in ASME A18.1 section 10.1.6:
(a) When an installation is placed out of service, all of the following requirements shall be met:
1. The power feed lines shall be disconnected from the machine disconnect switch or equivalent.
2. For a vertical platform lift, the doors or gates shall be secured against opening.
3. The department or agent municipality shall be notified.
4. The department or agent municipality may inspect the lift and charge an inspection fee.
5. Periodic inspections and tests may be discontinued while a lift is out of service.
6. Written approval of the building code authority where a conveyance is part of a required accessible route in an occupied building.
(b) Before the lift may be placed back into service, all applicable inspections and tests shall be performed as required by subs. (2) and (4) to (8), and the permit-to-operate requirements in s. SPS 318.1011 shall be met.
Note: The building code may prohibit placing a vertical or inclined platform lift out of service where used by persons with disabilities. Consult with a building inspector for written permission prior to placing it out of service.
(4)Routine inspections and tests. Substitute the following wording for the requirements in ASME A18.1 section 10.2.1: Routine inspections and tests of sections 2 and 3 lifts shall be performed at intervals of not longer than one year. Routine inspections and tests of section 4 lifts shall be performed at intervals of not longer than 3 years.
(5)Inspections and test requirements. Substitute the following wording for the requirements in ASME A18.1 section 10.2.2: Routine inspections shall include the applicable items listed in ASME A18.1 sections 10.2.2.1 to 10.2.2.4. Where an inspection reveals a need for a test to be conducted, the licensed elevator inspector may order the test.
(6)Periodic inspections and tests. Substitute the following wording for the requirements in ASME A18.1 section 10.3: Periodic inspections shall be performed at the same time as routine inspections. Where an inspection reveals a need for a test to be conducted, the inspector may order the test.
(7)Five-year inspection and test requirements.
(a) This is a department rule in addition to the requirements in ASME A18.1 section 10.3.3.1: Where a lift is equipped with a safety device that is subject to testing, the 5-year safety test – and where applicable, the governor test in ASME A18.1 section 10.3.3.2 – shall be performed. The test results shall be submitted to the department or agent municipality on an approved form.
Note:  Forms required under this chapter are available on the department’s website at https://dsps.wi.gov, or by request from the Department of Safety and Professional Services, P. O. Box 7302, Madison, Wisconsin 53708, or call (608) 266-2112.
(b) This is a department rule in addition to the requirements in ASME A18.1 section 10.1.3: The hydraulic control valves shall be tested in accordance with the requirements in ASME A17.1 8.10.3.2.2 (v).
(c) Substitute the following wording for the requirements in ASME A18.1 subsection 10.3.3.1 (b): For Type A safeties and Type A safety parts of Type C safeties, there shall be sufficient travel of the safety rollers or dogs remaining after the test to bring the platform and its rated load to rest on safety application at governor tripping speed. A metal tag shall be attached to the lift tower in a permanent manner that is readily visible to inspectors without disassembly, giving the date of the safety test together with the name of the person or firm who performed the test.
(8)Inspection and test requirements for altered installations. Substitute the following wording for the requirements in ASME A18.1 section 10.5: Where an alteration is made to an existing installation, the affected components shall comply with the applicable portions of ASME A18.1 sections 2 to 4, 8, and 9.
Note: Where plan submittal and approval and inspections are required under Table SPS 318.1007-4, inspections and tests are required as specified in subsection (2).
History: CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14; CR 19-118: cr. (3) (a) 6., am. (4), (5), renum. (7) to (7) (a), cr. (7) (b), (c) Register May 2020 No. 773, eff. 6-1-20.
SPS 318.1811Maintenance logs.
(1)Weekly operation procedure. The requirements in ASME A18.1 section 11.1.2 (c) are not included as part of this chapter.
(2)On-site documentation. This is a department rule in addition to the requirements in ASME A18.1 part 11.3: For a lift having an inspection and test panel, the inside cover of the inspection and test panel shall provide instructions for locating the on-site documentation. Instructions shall be permanently legible with lettering not less than 1/8 inch in height.
History: CR 19-118: cr. Register May 2020 No. 773, eff. 6-1-20.
Subchapter VI — Changes, Additions, or Omissions
to ANSI E1.42
SPS 318.4200Entertainment technology.
(1)General. Orchestra pit lifts shall be designed, constructed, installed, operated, maintained, tested, and inspected in accordance with ANSI E1.42, except as otherwise provided in this subchapter.
(2)Changes, additions, and omissions. Changes, additions, or omissions to ANSI E1.42 are specified in this subchapter and are rules of the department and are not requirements in ANSI E1.42.
Note: The sections in this subchapter are generally numbered to correspond with the chapter numbering in ANSI E1.42. For example, section SPS 318.4201 corresponds to ANSI E1.42 Chapter 1.
(3)Retroactivity. The operation, testing, maintenance, and periodic inspection requirements of this subchapter apply to all orchestra pit lifts existing prior to June 1, 2020.
(4)Pit access. Orchestra pit lifts installed after June 1, 2020, in accordance with this subchapter shall include a means to access the pit for use when the lift is at the lowest landing.
(5)Stage fall protection plan. An orchestra pit lift owner shall develop and implement a protection plan to address the hazard of stage edge falls.
Note: An example of a stage edge fall protection plan is available in ANSI E1.42 Annex B.
History: CR 19-118: cr. Register May 2020 No. 773, eff. 6-1-20.
SPS 318.4201Scope and application.
(1)The statement in ANSI E1.42 section 1.1.1.1 is not included as part of this subchapter.
(2)This is a department rule in addition to the requirements in ANSI E1.42 section 1.1.2: This subchapter covers the design, construction, operation, inspection, testing, maintenance, alteration, and repair of orchestra pit lifts and the associated parts, rooms, spaces, and hoistways.
(3)This is a department rule in addition to the requirements in ANSI E1.42 section 1.1.4: An orchestra pit lift that is not covered by this subchapter shall be subject to s. SPS 318.1700 (1).
History: CR 19-118: cr. Register May 2020 No. 773, eff. 6-1-20.
SPS 318.4202Reference codes, standards, and specifications. Substitute the following requirement for ANSI E1.42 section 2.1: All references listed in ANSI E1.42 section 2.2 are informational only and are not requirements of this subchapter.
History: CR: 19-118: cr. Register May 2020 No. 773, eff. 6-1-20.
SPS 318.4203Definitions.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.